Reference & Specs

The verified numbers behind every diagnosis this tool gives. The AI is grounded in this same data, so you can check its work. One rule throughout: the data plate on your actual equipment always overrides a generic range.

Measurement 01

Temperature split (Delta T)

The most useful measurement a homeowner can take. Subtract supply air temperature from return air temperature after the system has run 15 minutes.

ReadingWhat it meansWhere to look
16–22°FNormal cooling splitNo action needed
Below 16°FNot removing enough heatLow refrigerant charge, dirty condenser coil, failing compressor — pro diagnosis
Above 22°FNot enough air across the coilDirty filter, dirty evaporator coil, closed vents, weak blower — start DIY

Measuring it correctly

Keep the supply probe out of direct line-of-sight of the evaporator coil — radiant cold skews the reading low. High indoor humidity naturally pulls the split toward the bottom of the range; that alone isn't a fault. These targets assume roughly 400 CFM per ton of airflow; humid regions often commission at 350 CFM/ton, which shifts the targets.

Heating — temperature rise

Gas furnace temperature rise commonly falls in a 30–60°F band, but the correct range is printed on your furnace's data plate as a min/max (usually about a 30-degree spread), and that value governs. Rise above the plate maximum means restricted airflow and will eventually trip the high limit. Rise below the minimum means excessive airflow or an underfiring gas issue.

Regulation · Current as of 2026

The refrigerant change you need to know about

The biggest shift in residential HVAC in twenty years took effect this year, and most repair advice online hasn't caught up to it.

RefrigerantGWPSafety classStatus
R-22—A1Production and import ended 2020. Service only from reclaimed stock, expensive.
R-410A2,088A1 (non-flammable)No longer permitted for new installs. Existing systems legal to run and service.
R-454B466A2L (mildly flammable)Current standard for new equipment.
R-32675A2L (mildly flammable)Current standard for new equipment.
Jan 1, 2025

Manufacturers stopped producing new residential AC and heat pump equipment charged with R-410A, under the EPA's AIM Act Technology Transitions Rule.

Jan 1, 2026

New residential system installations must use a refrigerant with GWP of 700 or less. R-410A no longer qualifies for new installs.

Four things this changes for you

1. Your existing R-410A system is still perfectly legal to own, run, and repair — the rule restricts new equipment, not servicing installed ones. 2. You cannot retrofit an R-410A system to R-454B or R-32; they aren't drop-in compatible, so converting means full replacement. 3. R-410A prices are climbing as supply tightens, which shifts the repair-vs-replace math on an older system with a significant leak. 4. A2L refrigerants are mildly flammable — keep ignition sources away from a suspected leak on newer equipment. All refrigerant work still requires EPA Section 608 certification regardless of type.

One more thing worth knowing: refrigerant isn't consumed in normal operation. A system that's "low on refrigerant" has a leak. Adding more without repairing the leak is a temporary fix you'll pay for again.

Diagnostics

Furnace flash codes — read this before you Google yours

Flash codes are not universal

The same number of flashes means different things on different brands. On many Goodman furnaces 3 flashes indicates a pressure switch stuck open; on some Carrier units 3 flashes indicates a rollout or limit switch trip. Acting on the wrong brand's chart sends you down a completely wrong path. The authoritative source is the legend printed on the label inside your furnace's access panel or blower door. Read that first.

PatternCommon meaning (verify against your label)Frequent root cause
Slow steadyNormal standby, no call for heat—
RapidNormal — call for heat active—
Solid on / offControl board or power problemCheck power, then pro
1 flashOften ignition failure or flame senseDirty flame sensor, failed ignitor
2–3 flashesOften pressure switch faultClogged condensate drain, blocked flue or intake, cracked hose
4 flashesOften open high-limit switchDirty filter, blocked returns
5 flashesOften flame sensed when it shouldn't bePro diagnosis — gas valve

Count carefully. Watch at least three complete cycles before concluding — mistaking 3 flashes for 4 leads to entirely different troubleshooting. And a rollout switch trip is not the same as a limit trip: it means flame escaped the burner box. Shut down and call a pro immediately rather than resetting.

The technician's shortcut

Sequence of operation — where it fails tells you more than what failed

This is the single most useful diagnostic idea on this site. Instead of guessing at parts, find the step where the startup sequence stops.

StepWhat should happenIf it stops here
1Thermostat calls for heatThermostat, batteries, C-wire, breaker, door switch
2Inducer / draft motor startsControl board, inducer motor, thermostat wiring
3Pressure switch proves airflow, closesClogged condensate drain, blocked flue or intake, cracked hose
4Ignitor glowsCracked ignitor, control board
5Gas valve opens, burners lightGas supply, gas valve — pro only
6Flame sensor proves flameBurners light then die in 3–7 sec = dirty flame sensor. Classic.
7Blower starts after short delayBlower motor, capacitor, control board

Cooling is simpler: thermostat calls → contactor pulls in → outdoor fan and compressor start together → indoor blower starts. Outdoor fan running without the compressor, or the reverse, narrows the fault immediately. The blower-on delay after ignition is normal and exists to prevent cold air at the vents.

Airflow

Filters & MERV

MERVBest for
1–4Minimal filtration — protects equipment only
8–11Sweet spot for most homes
13+Better filtration, but only with a system and ducts sized for the added static pressure

Higher MERV is not automatically better — a filter more restrictive than your system was designed for chokes airflow, which can freeze the evaporator coil and overwork the blower. Change 1-inch pleated filters every 1–3 months (monthly with pets); 4–5 inch media filters run 6–12 months. The airflow arrow points toward the blower.

Electrical

Capacitors

The most common cause of "compressor hums but the fan won't spin" and "clicks but won't start." Typical life is 5–10 years; heat and power surges shorten it.

  • Failure signsBulging or domed top, oily residue, rust, split casing
  • RatingPrinted in microfarads (MFD/µF) plus voltage. Dual-run caps show two values, e.g. 45+5 MFD (compressor + fan)
  • ReplacementMust match MFD and meet or exceed voltage rating
  • SafetyHolds a dangerous charge after power is off — call a pro

While you wait for service

Shut the system off at the thermostat. Running a humming compressor with no fan airflow can overheat and destroy it.

Planning

Lifespan & repair-vs-replace

ComponentTypical service life
Central AC / heat pump12–15 years
Gas furnace15–20 years
Capacitor5–10 years

A common heuristic: if repair cost × system age in years exceeds replacement cost, replacement is usually better value. Treat it as a rule of thumb, not a rule. A single failed capacitor or contactor on an otherwise healthy 10-year-old system is normally worth repairing.

On efficiency ratings: SEER2/EER2/HSPF2 replaced the older SEER/EER/HSPF test procedures in 2023. SEER2 numbers read slightly lower for equivalent equipment, so comparing your old unit's SEER to a new unit's SEER2 overstates the improvement.

Prevention

Seasonal maintenance

  • Monthly–quarterlyCheck and change the filter
  • SpringClear 2 ft around the outdoor unit, rinse the condenser coil inside-out with power off, flush the condensate drain, test cooling before the first heat wave
  • FallNew filter, test heat early, verify CO detectors, clear flue and intake terminations of debris and nests
  • Year-roundKeep landscaping, fencing, and dryer vents clear of the outdoor unit

Don't fully cover the outdoor unit in winter

Trapped moisture promotes corrosion and full covers invite rodents. A top-only cover is the usual compromise. Heat pumps must stay uncovered — they run all winter.